Regular maintenance of the centrifuge

1. Inspection of the vacuum system The current ultracentrifuge (high-speed centrifuge without vacuum system) mostly uses a mechanical rotary vacuum pump and an oil diffusion pump two-stage vacuum system, the vacuum can reach 10-3mmHg, which greatly reduces the air. The frictional resistance and the temperature generated by the friction increase. In order to ensure the degree of vacuum in the centrifugal chamber, the frosted surface of the surface should be wiped clean before being placed on the rotating shaft, and then into the centrifugal chamber, and then the vacuum pump is started to evacuate. In addition, during the long-term operation of the centrifuge, some water will be immersed in the scoop pump to mix with the oil. Therefore, in each inspection, the oil drain switch at the bottom of the vacuum pump should be opened, the water should be drained, and then the accessory funnel should be inserted into the oil pipe of the oil drain port, and the MR-100 vacuum oil should be added to the oil level observation center mark. If the line height is found to be too dirty and black before draining, it should just be released and replaced. After the above inspection, it is checked whether the ethylene pipe under the oil sump is filled with oil. If oil accumulation is found, the oil mold separator is blocked, so it is necessary to unscrew the oil mist separator top mother screw, remove the top cover, and withdraw the filter element to replace the vacuum in the centrifugal chamber, in addition to the performance of the vacuum pump itself. In addition to the fault, it is also related to the sealing of the sealing rubber ring, shaft sleeve and pipe of the instrument door. It is found that the air leak should be repaired immediately, especially for the parts and interfaces of the laboratory equipment. A The pressure of the tap water itself is not enough; the repair of the lubricant by the loop system can deform the spring of the switch. The water pressure is not an important part of the centrifuge, so the dust of the cold heat exchanger should be removed during maintenance. Dust in the wall of the cold heat exchanger and on the radiator can affect the performance of the cold heat exchanger, causing excessive internal pressure and aggravating the load on the compressor components, causing damage to system components. Another component to be aware of is the filter dryer. If the dirt is stuffed or the desiccant (silica gel) ages, the refrigeration system will not be able to cool. At this point, the filter screen of the filter dryer should be removed, the copper filter should be cleaned with gasoline, the desiccant should be replaced, and then installed. Other common faults are: The compressor can't start; the compressor can start but the temperature can't drop; it can lower the temperature but it takes a long time. The cause of these failures may be the F z fuse burnout in the control box, the motor short circuit in the compressor, the leakage of the piping system, the refrigerant: the ice or the ice block of the expansion valve.
The lubrication circulation system not only acts as a lubricating mechanical structure, but also acts as a cooling and oil seal. Therefore, to ensure the purity of the oil, regularly clean the oil filter and piping to prevent blockage. If it is found that there is sediment in the oil bottle or the oil turns black, it is necessary to replace the new oil to avoid serious damage to the inside of the structure (gear joint, sliding shaft seal). Both the refrigeration system and the vacuum system use soapy water for leak detection. The method is: dissolve the soap with warm water, then add a few drops of glycerin, apply it to the preparation interface, and carefully observe whether there is gas trapping.
2. When the system is overhauled, the principle and operation procedure should be understood in detail. The mechanical structure diagram should be compared with the real object. Familiar with the position and function of all parts inside the instrument and the direction of the wire connection on the terminal block. The program checks step by step and gradually troubleshoots.
Common faults of this system are:
(1) The water pressure switch cannot be turned on. The reason is
1 contact poor contact
2 The bellows of the pressure switch is broken, the scale is blocked, the fatigue is long-term, or the mechanical components are loose.
(2) The oil pressure switch cannot be turned on for the following reasons;
A insufficient oil;
B oil circulation pump has failed;
C oil pressure switch is damaged;
D Contact contact is poor.
(3) The vacuum switch cannot be turned on for the following reasons;
A vacuum pump vacuum function is reduced;
B vacuum pressure is too low;
C vacuum system leakage;
D Contact contact is poor.
When the failure of the oil pressure switch, water pressure switch and vacuum pressure switch has not been determined, the pressure of the pressure spring cannot be adjusted at will. If you adjust the changes at will, the fault may be more expanded. If the pressure is raised, the technical indicators will not meet the requirements, the whole system can not be started, and the procedures for troubleshooting are added. If the pressure is lowered, the operating conditions of the instrument cannot be met, resulting in damage to other parts of the instrument. If it is determined that the pressure fault can be adjusted strictly according to the conditions required by the manual, such as the water pressure switch is 2 liter / minute flow, the vacuum switch is 8 × 10 ~ mmHg. If the contact is black due to excessive current, it will form irregularities or dirt, which will make the contact bad. It should be cleaned and trimmed in time. The blackened joints should be lightly polished with a bamboo bag E-deer skin, but the hammer or coarse sand paper is forbidden, as this will damage the protective layer of the joint, and the dirt can be cleaned with a sand cloth. Components that cannot be repaired must be replaced and cannot be used in order to prevent the expansion of the fault. In addition to the failure of each of the above pressure switches, abnormalities in the relay can also hinder the smoothness of the circuit. Frequent faults in relays;
A relay vibrates and does not suck well well;
There is no voltage at both ends of the B-line package. It is not good to open the relay contacts. First, check whether the voltage across the relay is normal. The terminal voltage cannot be lower than the rated value of 85. Under normal conditions, the vibration of the relay does not attract well. The reason is that the reaction force is greater than the suction force, and the reaction force depends on the reaction spring. The armature moves the frictional resistance. Therefore, attention should be paid to whether the shaft or other moving parts are stuck or not, so that the friction is increased. If this is not the case, the stroke can be reduced by adjusting the stroke screw of the relay if necessary. This is because as the stroke is reduced, the gap is also reduced, the resistance in the magnetic circuit is also reduced, the magnetic flux is correspondingly increased, and the suction force is also increased. It is also possible to reduce the spring pulling force of the reaction force, thereby reducing the reaction force. But be sure to disconnect the contacts when there is no voltage at both ends of the line package. Contact contact failure can be eliminated according to the above pressure switch contact processing method. The inspection of the instrument operating state control circuit can be carried out by referring to the circuit schematic attached to each centrifuge and the data given and the waveform of each point. Test instruments used in maintenance such as digital frequency meters, Nordic watches and multimeters should be accurate and reliable to avoid making false judgments. When welding parts and wires, the quality of the weld should be guaranteed. Flux oil can be used for flux and corrosive flux is not allowed. The electric ferrochrome used should have a suitable power. When soldering semiconductor components, the soldering temperature should be too high and the time should be too long to avoid damage to the components and the printed board copper foil.
(4) Common faults in the speed control part:
A instrument can't start, can't adjust speed and steady speed;
B Speed ​​up too fast:
C can not automatically stop when it is too fast;
D Do not deflate after low speed or shutdown.
The instrument cannot be started. Check that the indicator light is intact. If the indicator light is normal, the reason why it cannot be started is of course that the starting condition has not been met, and it should be checked step by step according to the driving conditions. First check that the positions of the knobs on the control panel are correct, and then check the start conditions one by one. Typical starting conditions include: the closed state of the door, the water pressure switch, the oil pressure switch, the vacuum in the centrifugal chamber, and the position of the timing controller. If the condition is still not activated, check the start control circuit, including the control line's insurance, power supply, voltage at each working point, and operating parameters of each component. The overspeed line is a differential amplifier with a fixed signal at one end and a feedback signal for the actual speed at the other end. Comparing the two, if the overspeed line loses control, the instrument will not operate normally. Usually, the original sleepy is the failure of the feedback signal generated by the actual speed or the components of the photoelectric speed measuring device and the control circuit. The control principle that the low speed cannot be deflated is also the differential amplifier, and the test is the same as that of Fan Guo. In addition, check whether the bleed valve and vent hole are unobstructed.

We have many different kinds of other shape Lip Gloss Case.Any injection color is avaliable for the empty plastic cosmetic lip gloss case.Spray painting/UV coating/metallized are also available for the lip gloss case.

MOQ

12.000pcs

Delivery time

50-55days

Material

AS,ABS

color

Injection color,spray coating color,UV and metalizing color

logo

Silk screan and hot staping

Packing

paper carton

Place of Origin

Zhejiang

We promise out standing service tailored to meet your demands. Our products are favored by many customers all over the world and are sold in Europe, North America, South America and Asia.

We are looking forward to your E-mail and establishing cooperative relationship with you! We would provide professional lip gloss case with good services for you. 

LG-374CLG-356

Other Shape Lip Gloss Case

Other Shape Lip Gloss Case, Odd Shaped Lip Gloss Tube, Lip Gloss Packaging

ims Packaging Limited , https://www.ims-cosmetic-packaging.com

Posted on